Notes:
1.
The return value “01” means DI Inactive/ DO Operated/Alarm (including Setpoint & Diagnosis); and the return value “00”
means DI Active/ DO Released/Setpoint Return.
2.
The returned Event Value (for SOE Event Classification=Setpoint only) is in Float format, and please refer to Table 5-40 to
check the Unit for each parameter.
SOE Classification
Event
Classification
Sub-
Classification
Status Event Value
Description
1=DI Changes
1
1/0
DI1 Inactive / DI1 Active
2
1/0
DI2 Inactive / DI2 Active
3
1/0
DI3 Inactive / DI3 Active
4
1/0
DI4 Inactive / DI4 Active
2=DO Changes
1
1/0
DO1 Operated/Released
by Remote Control
2
1/0
DO2 Operated/Released
by Remote Control
3~10
Reserved
11
1/0
DO1 Operated/Released by Setpoint
12
1/0
DO2 Operated/Released by Setpoint
13~20
Reserved
21
1/0
DO1 Operated/Released by Front Panel
22
1/0
DO2 Operated/Released by Front Panel
23~30
Reserved
31
0
DO1 Released when Pulse Time out
32
0
DO2 Released when Pulse Time out
3=Setpoint
1
1/0
Trigger
Value /
Return
Value
Over Uln Setpoint Active/Return
2
1/0
Over Ull Setpoint Active/Return
3
1/0
Over Current Setpoint Active/Return
4
1/0
Over In Setpoint Active/Return
5
1/0
Over Frequency Setpoint Active/Return
6
1/0
Over kW Total Setpoint Active/Return
7
1/0
Over kvar Total Setpoint Active/Return
8
1/0
Over kVA Total Setpoint Active/Return
9
1/0
Over PF Total Setpoint Active/Return
10
1/0
Over kW Total Present Demand Setpoint
Active/Return
11
1/0
Over kvar Total Present Demand
Setpoint Active/Return
12
1/0
Over kVA Total Present Demand Setpoint
Active/Return
13
1/0
Over kW Total Predicted Demand
Setpoint Active/Return
14
1/0
Over kvar Total Predicted Demand
Setpoint Active/Return
15
1/0
Over kVA Total Predicted Demand
Setpoint Active/Return
16
1/0
Over Voltage THD Setpoint Active/Return
17
1/0
Over Voltage TOHD Setpoint
Active/Return
18
1/0
Over Voltage TEHD Setpoint
Active/Return
19
1/0
Over Current THD Setpoint
Active/Return
20
1/0
Over Current TOHD Setpoint
Active/Return
21
1/0
Over Current TEHD Setpoint
Active/Return
22
1/0
Over Voltage Unbalance Setpoint
Active/Return
23
1/0
Over Current Unbalance Setpoint
Active/Return
24
1/0
Reversal Phase Setpoint Active/Return
25
1/0
Over I4 Setpoint Active/Return
26
1/0
Over AI Setpoint Active/Return
27
Over Ir (Residual Current) Setpoint
Active/Return