CET Electric Technology
95
DNP Point Map
Object 1 - Binary Input Status with Flags (Included in Class 0 responses)
Read with Object 1, Variation 2, and Qualifier 6.
Point
Description
Format
Range
0
DI1
1
UINT8
Bit Flags
1
DI2
1
UINT8
Bit Flags
2
DI3
1
UINT8
Bit Flags
3
DI4
1
UINT8
Bit Flags
Supported Flags:
Bit 0 (ONLINE):
0=Offline, 1=Online
Bit 7 (STATE):
0=Off, 1=On
Notes:
1)
If the Device Model does not support DI, the Bit 0 and Bit 7 for the bytes of all DI status above would be set to “0”.
Object 10 - Binary Output States (Included in Class 0 responses)
Read with Object 10, Variation 2, and Qualifier 6.
Point
Description
Format
Range
0
Reserved
UINT8
1
Clear All Energy Registers
UINT8
Always 0
2
Reserved
UINT8
3
Clear Peak Demand of This Month (Since Last Reset)
UINT8
Always 0
4
Clear All Demand Registers
UINT8
Always 0
5
Clear Max/Min Logs of This Month (Since Last Reset)
UINT8
Always 0
6
Clear All Max./Min. Log
UINT8
Always 0
7
Clear Device Operating Time
UINT8
Always 0
8
Clear All Data
UINT8
Always 0
9
Clear DI1 Pulse Counter
UINT8
Always 0
10
Clear DI2 Pulse Counter
UINT8
Always 0
11
Clear DI3 Pulse Counter
UINT8
Always 0
12
Clear DI4 Pulse Counter
UINT8
Always 0
13
Reserved
UINT8
14
Reserved
UINT8
15
Clear All Pulse Counters
UINT8
Always 0
16
DO1
UINT8
Bit Flags
17
DO2
UINT8
Bit Flags
18
Reserved
UINT8
19
Reserved
UINT8
20-29
Reserved
30-43
Wiring Diagnostics Status
1
UINT8
Bit Flags
Notes:
1)
The following table shows the details of Point 30-43.
No.
Event
30
Frequency is out of range (45 to 65Hz) (3P4W or 3P3W)
31
Any phase voltage < 10% of PT Primary (Register 6000) (3P4W only)
32
Any phase current < 10% of CT Primary (Register 6004) (3P4W or 3P3W)
33
Reserved
34
Reserved
…
Voltage Phase Reversal (3P4W only)
Current Phase Reversal (3P4W or 3P3W)
Negative kW Total may be abnormal (3P4W or 3P3W)
Negative kWa is may be abnormal (3P4W only)
Negative kWb may be abnormal (3P4W only)
Negative kWc may be abnormal (3P4W only)
CTa polarity may be reversed (3P4W only)
CTb polarity may be reversed (3P4W only)
43
CTc polarity may be reversed (3P4W only)
44
Disconnection of Residual Current Input
Supported Flags:
Bit 0 (ONLINE):
0 = Offline, which represents that the control of the Output could not be implemented.
1 = Online, which represents that the Output works properly, once control request has been sent, the command could be
correctly implemented.
Bit 7 (STATE):