CET Electric Technology
23
EN Pulse CNST
Pulse Constant
1000/3200/6400
1000
LED EN Pulse
Enable kWh/kvarh Energy
Pulsing
Disabled/kWh/kvarh
kWh
EN Period
Interval Energy period
5 to 60 min
60
kvarh Calc.
kvarh Calculation Method
RMS/FUND
RMS
OT Threshold
Current Threshold of Device
Operating Time
1 to 1000 (x0.001In)
1
S.R. Mode
Self-Read Mode to both Peak
Demand and Max/Min Log
Auto/Manual
Manual
S.R. Time
Self-Read Time to both Peak
Demand and Max/Min Log
See Note 4)
--D--H
Comm.
RS485 (P1)
Protocol
Protocol
Modbus/BACnet/
DNP/Gateway
Modbus
Unit ID
Modbus Address
Modbus: 1 to 247
BACnet: 1 to 247
DNP: 0 TO 65519
100
Baud Rate
Data rate in bits per second
1200/2400/4800/
9600/19200/38400
9600
Data Format
Data Format
8N2/8O1/8E1/
8N1/8O2/8E2
8E1
Ethernet (P2)
IP Address
Ethernet IP Address
192.168.0.100
Subnet Mask
Ethernet Subnet Mask
255.255.255.0
Gateway
Ethernet Gateway
192.168.0.1
Setpoint
Group #1
Type
Whether and how the
Setpoint is triggered
0 = Disabled;
1 = Over Setpoint
2 = Under Setpoint
0
Parameter
The parameter to be
monitored.
See Note 5)
None
OvLim
Over Limit
0
UnLim
Under Limit
0
ActiveDelay
Active Delay
0 to 9999s
0
InactiveDelay
Inactive Delay
0 to 9999s
0
Trigger1
Setpoint Trigger1
See Note 6)
Trigger2
Setpoint Trigger2
See Note 6)
…
Group #9
Type
Whether and how the
Setpoint is triggered
0 = Disabled;
1 = Over Setpoint
2 = Under Setpoint
0
Parameter
The parameter to be
monitored.
See Note 5)
None
OvLim
Over Limit
0
UnLim
Under Limit
0
ActiveDelay
Active Delay
0 to 9999s
0
InactiveDelay
Inactive Delay
0 to 9999s
0
Trigger1
Setpoint Trigger1
See Note 6)
Trigger2
Setpoint Trigger2
See Note 6)
I/O
Digital Input
Function
DI Function
DI1~DI3
Function Mode for DI1 to DI4
Digital Input /
Pulse Counter /
TOU Control
Digital Input
DI4
Digital Input /Pulse
Counter
Debounce
Specifies the minimum duration the DI must remain in the Active or Inactive
state before a state change is considered to be valid.
DI1
Debounce for DI1 to DI4
1 to 9999 ms
20 ms
…
DI4
Pulse Weight
Specifies the incremental value for each pulse received
DI1
Pulse Weight for DI1 to DI4
1 to 1000000
1