CET Electric Technology
72
5.10 Data Recorder Log
Register
Property
Description
Format
20000~20037
RO
DR Log #1 Buffer
See Table 5-32
Standard DR Log Structure
20038~20075
RO
DR Log #2 Buffer
20076~20113
RO
DR Log #3 Buffer
20114~20151
RO
DR Log #4 Buffer
20152~20189
RO
DR Log #5 Buffer
Table 5-31 DR Log
Offset
Property
Description
Format
+0
RW
DR Log X Pointer
UINT32
+2
RO
High-order Byte: Year (0-99)
Low-order Byte: Month (1-12)
UINT16
+3
RO
High-order Byte: Day (1-31)
Low-order Byte: Hour (0-23)
UINT16
+4
RO
High-order Byte: Minute (0-59)
Low-order Byte: Second (0-59)
UINT16
+5
RO
Millisecond
UINT16
+6~+7
RO
Parameter #1
Float
+8~+9
RO
Parameter #2
+10~+11
Parameter #3
…
…
+36~+37
RO
Parameter #16
Table 5-32 DR Data Buffer Structure
Notes:
1)
Writing n to the DR Log X Pointer register will load the Log Record at pointer position n into the DR Log X Buffer from the
device’s memory.
2)
Writing a pointer value that points to a Log Record that is either already expired or has not been generated yet to the DR
Log X Pointer register will generate an exception response with the Illegal Data Value error code (0x03) as defined by the
Modbus protocol.
5.11 Device Setup
5.11.1 Basic Setup Parameters
Register
Property
Description
Format
Range, Default*
6000
RW
PT Primary
1
UINT32
1 to 1,000,000 V, 100*
6002
RW
PT Secondary
UINT32
1 to 690V, 100*
6004
RW
CT Primary
UINT32
1 to 30,000A, 5*
6006
RW
CT Secondary
UINT32
1 to 5A, 5*
6008~6010
RW
Reserved
6012
RW
I4 Primary
UINT32
1 to 30,000A, 5*
6014
RW
I4 Secondary
UINT32
1 to 5A, 5*
6016~6018
RW
Reserved
6020
RW
Wiring Mode
UINT16
0=DEMO, 1=1P2W L-N,
2=1P2W L-L, 3=1P3W L-L-N
4=3P3W, 5=3P4W*
6021
RW
PF Convention
UINT16
0=IEC*, 1=IEEE, 2=-IEEE
6022
RW
kVA Calculation
UINT16
0=Vector*, 1=Scalar
6023
RW
Ia Polarity
UINT16
0=Normal*, 1=Reverse
6024
RW
Ib Polarity
UINT16
6025
RW
Ic Polarity
UINT16
6026~6027
RW
Reserved
6028
RW
THD Calculation
2
UINT16
0= THDf*, 1= THDr
6029
RW
Demand Period
UINT16
1 to 60 (minutes), 15*
6030
RW
Number of Sliding Windows
UINT16
1 to 15, 1*
6031
RW
Predicted Response
UINT16
70 to 99, 70*
6032
RW
Arm before Execute
UINT16
0=Disabled*, 1=Enabled
6033
RW
Self-Read Time
3
UINT16
0*
6034
RW
Monthly Energy Log Self-Read
Time
4
UINT16
0*
6035
RW
Energy Pulse Constant
UINT16
0=1000 imp/kxh*
1=3200 imp/kxh
2=6400 imp/kxh
6036
RW
LED Energy Pulse
UINT16
0=Disabled
1=kWh*
2=kvarh