CET Electric Technology
16
2.
For the DI Status register, the bit values of B0 to B2 represent the states of DI1 to DI3, respectively, with “1” meaning Active (Closed)
and “0” meaning Inactive (Open).
3.
For the Disconnect Relay Status register, the returned value “1” means Connected while “0” means Disconnected.
4.
The PMC-230 has one SOE Log and one DR Log. Each of these logs has a Log Pointer that indicates its current logging position. The ran ge
of the Log Pointer is between 0 and 0xFFFFFFFF, and it is incremented by one for every new log generated and will roll o ver to 0 if its
current value is 0xFFFFFFFF. If a Clear Log is performed through the Front Panel or via communications, its Log Pointer will be reset to
zero, and the SOE Log Pointer will be immediately incremented by one with a new “Clear SOE” event. When the number of events is
larger than the Log Depth, only the latest 32 SOE logs or up to 65,535 DR Logs will be stored on a FIFO basis.
The latest log location can be determined as Latest Log Location = Modulo [
Log Pointer
/
Log Depth
], where
Log Pointer
is either the SOE Log Pointer or DR Log Pointer and
Log Depth
is fixed at 32 for the SOE Log Depth or the DR Recording Depth (see
Section 5.9
5.2
Real Time Energy Measurements
Register
Property
Description
Format
Scale
Unit
0500
RW
kWh Import
INT32
x0.01
kWh
0502
RW
kWh Export
INT32
0504
RW
kvarh Import
INT32
kvarh
0506
RW
kvarh Export
INT32
0508
RW
kVAh
INT32
kVAh
0510
RW
kWh Import of T1
INT32
kWh
0512
RW
kWh Export of T1
INT32
0514
RW
kvarh Import of T1
INT32
kvarh
0516
RW
kvarh Export of T1
INT32
0518
RW
kVAh of T1
INT32
…
0520~0538
…
…
INT32
kWh
0540
RW
kWh Import of T4
INT32
kWh
0542
RW
kWh Export of T4
INT32
0544
RW
kvarh Import of T4
INT32
kvarh
0546
RW
kvarh Export of T4
INT32
0548
RW
kVAh of T4
INT32
kVAh
Table 5-2 Energy Measurements
5.3
DI Pulse Counter
Register
Property
Description
Format
Range/Unit
1200
RW
DI1 Pulse Counter
INT32
0 to 99,999,999
1202
RW
DI2 Pulse Counter
INT32
1204
RW
DI3 Pulse Counter
INT32
Table 5-3 DI Pulse Counter
5.4
Harmonic Measurement
Register
Property
Description
Format
Scale/Unit
1300
RO
I THD
Float
x1, 0.1 means 10%
1302
RO
U THD
Float
Table 5-4 Harmonic Measurements
5.5
Demand Measurements
5.5.1
Present Demand
Register
Property
Description
Format
Scale
Unit
3000
RO
U
Float
x1
U
3002
RO
I
Float
A
3004
RO
P
Float
kW
3006
RO
Q
Float
kvar
3008
RO
S
Float
kVA
Table 5-5 Present Demand
5.5.2
Max. Demand of This Month (Since Last Reset)
Register
Property
Description
Format
Scale
Unit
3400~3405
RO
U
See
x1
U
3406~3411
RO
I
A
3412~3417
RO
P
kW
3418~3423
RO
Q
kvar
3424~3429
RO
S
kVA
Table 5-6 Max. Demand of This Month