CET Electric Technology
10
3.5.3
Configurations
The Setup Configurations mode provides access to the following setup parameters:
Label
Parameters
Description
Option (value)
Default
PROG
Programming
Setup Configuration Mode
/
/
PW
Password
Enter Password
0~9999
0
SET PW
Set Password
Enter New Password
0~9999
-
DISC
Disconnect
Switch the Disconnect Relay Off/On
ON/OFF
ON
PF
PF Convention
PF Convention
IEC, IEEE, -IEEE
IEC
Id
Unit ID
COM Unit ID
1~247
100
Bd
Baud Rate
Data rate in bits per second (bps)
1200/2400/4800/
9600/19200
9600
CFG
COM Port
Configuration
Data Format
8N2/8O1/8E1/8N1
8E1
nUM
# of Windows
No. of Windows for Demand Calculation
1~15
1
PErIod
Period
Demand Period
0~60 (min)
5(min)
LEd
LED Energy Pulsing
Configure LED Energy Pulsing
OFF/kWh/kvarh
kWh
do
DO Energy Pulsing
Configure DO Energy Pulsing
OFF/kWh/kvarh
kWh
CLr En
Clear Energy
Clear All Energy
YES/No
No
CLr
dMd
Clear Demand
Clear All Demand
YES/No
No
CLr DI
Clear DI
Clear All DI counters
YES/No
No
Clr oT
Clear Operating Time
Clear running hours for device
YES/No
No
CLr SoE
Clear SOE
Clear SOE
Yes/No
No
CLr Cnt
Clear Counters
Clear both FP & COM Setup Counters
YES/No
No
Set Date
Enter the Current Date
YY-MM-DD
/
Set Clock
Enter the Current Time
HH:MM:SS
/
FW
Firmware Version
Firmware Version
For example, 10002
means the firmware
version is V1.00.02.
/
Firmware Date
Firmware Version Date
YYMMDD
/
PROT
Protocol
Protocol Version
e.g. 1.1 means V1.1
/
SN
The left 5 digits
The left 5 digits of SN
XXXXX
/
The right 5 digits
The right 5 digits of SN
YYYYY
/
Table 3-1 Configuration