SOE Classification
Event
Classification
Sub-
Classification
Status
Event
Value
Description
1=DI Changes
1
1/2
0
1=DI1 Inactive, 2=DI1 Active
2
1/2
0
1=DI2 Inactive, 2=DI2 Active
3
1/2
0
1=DI3 Inactive, 2=DI3 Active
2=Relay Status
1
1/2
0
1=Relay Operated, 2=Relay Released
via Comm.
2
1/2
0
1=Relay Operated, 2=Relay Released
via the Front Panel
4=Self-diagnostic
1
0
0
Flash Fault
2
0
0
FRAM Fault
3
0
0
System Parameters Fault
5=Operations
1
0
0
Power On
2
0
0
Power Off
3
0
0
Clear All Energy via Front Panel
4
0
0
Clear All Demand via Front Panel
5
0
0
Clear All DI Counters via Front Panel
6
0
0
Clear Operating Time via Front Panel
7
0
0
Clear SOE via Front Panel
8
0
0
Clear Setup Counters via Front Panel
9
0
0
Set Clock via Front Panel
10
0
0
Setup Changes via Front Panel
11 to 20
--
--
Reserved
21
0
0
Clear Real Time Energy via Comm.
22
0
0
Clear Historical Monthly Energy Log via Comm.
23
0
0
Clear Present Monthly Energy via Comm.
24
0
0
Clear All Energy Logs via Comm.
25
0
0
Clear Max. Demand of This Month via Comm.
26
0
0
Clear All Demand via Comm.
27
0
0
Clear All Data via Comm.
28
0
0
Clear SOE via Comm.
29
0
0
Clear All DI Counters via Comm.
30
0
X=1 to 3
Clear DIx Counter via Comm.
31
0
0
Clear Operating Time via Comm.
32
0
0
Factory Restore via Comm.
33
0
0
Setup Changes via Comm.
34
0
0
Preset Energy via Comm.
35
0
0
Preset TOU Energy via Comm.
36
0
1 to 4
Switch TOU Schedule
37
0
0
Clear Data Recorder via Comm.
38
0
0
Clear Setup Counters via Comm.
39
0
0
Set Clock via Comm.
40
0
0
Communication locked out for 15 minutes after
3 incorrect password attempts!
Table 5-13 SOE Classification
Note:
1.
The event values of
Switch TOU Schedule
are illustrated in the table below:
Record Value
Description
1
Switch Schedule 1 to Schedule 2 manually
2
Switch Schedule 2 to Schedule 1 manually
3
Switch Schedule 1 to Schedule 2 automatically
4
Switch Schedule 2 to Schedule 1 automatically
Table 5-14 TOU Switch Records