Ceiec Electric Technology
22
RTU Model:
Option
Description
Setting
IP Address
Configure the PMC-1304-3’s IP address
Default IP1 = 192.168.0.127
Default IP2 = 192.168.1.127
Subnet Mask
Configure the Subnet Mask
Default = 255.255.255.0
Default Gateway
Configure the Default Gateway’s IP address
Default = 192.168.0.1
DNS1/DNS2
Configure the Domain Name System (DNS) that
connected to the network. The two parameters
are only available in the RTU Model.
Default =Null
Notes:
1)
The IP addresses for the two Ethernet ports must be in different subnets.
2)
The Default Gateway must be in the same subnet as one of the IP addresses.
3)
Click <
Submit
> at the upper left-hand corner of the right-hand pane to store the new
configuration in a local cache before leaving this page.
4)
Save configuration.
For on-line mode, click <
Save>
at the upper right-hand corner of the web page to save the
new configuration and it will be take effect only after the device reboots.
For off-line model, click <
Save>
at the upper right-hand corner of the web page to save the
new configuration to the device’s configuration file that is stored on the PC for Off-Line
programming and then synchronize the new configuration to the device via
System
Maintenance > Backup/Restore > Synchronization Settings
menu.
5)
Click <
Quit
> to leave the PMC-1304-3 Web Console. Please ensure that your changes have
been saved before leaving.
4.3.1.2 Time Settings
This option exists in both the On-Line and Off-Line programming modes, but only for the RTU Model.
Click on
Time
under
Device Settings
on the left-hand pane and the following screen appears. Click
<
Submit>
and <
Save>
to save your changes after modification.