Ceiec Electric Technology
42
+4
RO
High-order Byte: Year (-2000)
UINT16
0-99 (Year-2000)
Low-order Byte: Month
1 to 12
+5
RO
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
+6
RO
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
+7
RO
Millisecond
UNIT16
0 to 999
+8
RO
Event Value
2
Float
-
Table 5-6 SOE Log Data Structure
Notes:
1)
The unit ID is the actually communication ID. Only the last 2 characters will be uploaded if ID is
longer than 4 characters, for example a device’s unit ID is 123456789012, then only 12 will be
uploaded.
2)
Please refer to connected device’s user manual to find the event meaning. Invalid operation
will be recorded as 0x7fffffff.
5.6 Time
Register
Property
Description
Format
Note
60000
WO
High-order Byte: Year
UINT16
1-37 (Year-2000)
Low-order Byte: Month
1 to 12
60001
WO
High-order Byte: Day
UINT16
1 to 31
Low-order Byte: Hour
0 to 23
60002
WO
High-order Byte: Minute
UINT16
0 to 59
Low-order Byte: Second
0 to 59
60003
WO
Millisecond
UINT16
0 to 999
Table 5-7 Time Registers
5.7 Data Recorder Log
The PMC-1304-3’s real-time data, including AI and PI, is recorded as data recorder log. A DR log
records all of the AI and PI data in data cache at a certain moment. As for recording depth, users can
configure via the
Data Export
web interface under
Data Cache Management
>
Cache Management
menu.
Register
Property
Description
Format
30000
RO
DR Log Index
UINT32
30002
RW
Current DR Log Pointer
UINT32
30004
RO
DR Depth
UINT16
30005
RO
High-order Byte: Year
UINT16
Low-order Byte: Month
30006
RO
High-order Byte: Day
UINT16
Low-order Byte: Hour
30007
RO
High-order Byte: Minute
UINT16
Low-order Byte: Second
Table 5-8 Data Recorder Log