Ceiec Electric Technology
13
Before installation, make sure that the DIN rail is already in place
Move the installation clip at the bottom of the PMC-1304-3 downward to the “unlock” position
Mount the PMC-1304-3 on the DIN rail
Push the installation clip upward to the “lock” position to secure the PMC-1304-3 on to the DIN
Rail
Figure 2-3 DIN-Rail Mounting
Surface Mounting
Installation steps:
Pre-drill the mounting holes based on the mounting diagram as shown in Figure 2-4
Fit the device through the cutout
Use four screws to fix the device tightly against the panel
Figure 2-4 Surface Cutout Mounting
2.4 Power Supply Wiring
Please consult the serial number label to ensure that the supply voltage is within the range of the
PMC-1304-3’s power supply specifications.
For AC supply, connect the live wire to the L/+ terminal and the neutral wire to the N/- terminal.
For DC supply, connect the positive wire to the L/+ terminal and the negative wire to the N/- terminal.