Note: The batteries in the UPS are rated for a 3-5 year service life. The length
of service life depends on the frequency of usage and ambient temperature.
Batteries used beyond expected service life will often have severely reduced
runtimes. Replace batteries at least every 5 years to keep units running at
peak efficiency.
6.2 Transporting the UPS
NOTE: The internal UPS batteries MUST be disconnected before transport.
CAUTION: The following procedure should be performed or supervised by
personnel knowledgeable about batteries and the required precautions.
If the UPS requires any type of transportation, the batteries must be
disconnected (but not removed) before the unit is transported:
1.
Verify that the UPS is off and disconnected from utility power.
2.
Place the UPS on a flat, stable surface with the front of the cabinet facing
you.
3.
Remove the UPS front cover
4.
Disconnect the internal battery connectors
5.
Replace the UPS front cover
6.3 Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by
connecting the UPS to utility power. The batteries charge to 90% capacity in
approximately 4 hours. However, it is recommended that the batteries charge
for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has
passed and the batteries were never recharged, do not use the UPS. Contact
your service representative.
When to Replace Batteries
When the status summary screen displays the UPS fault icon with the “Service