49
Figure. 5-17 Measurement menu tree
5.4.5 The control menu
By pressing
on the menu “Control”, the display will enter the next
control menu tree.
1)
Start Battery Test: this instructs the UPS to do the battery test.
2)
Clear EPO status: once the EPO status is enabled, the UPS output will
be cut off. To recover to normal status, first the EPO connector
should be closed, and enter this menu to clear EPO status, then the
UPS will stop the alarm and recover to Bypass mode. The UPS should
be turned on by manual operation.
3)
Reset Fault status: when a fault occurs, the UPS remains in Fault
mode and alarms. To recover to normal status, enter this menu to
reset error status, then the UPS will stop the alarm and recover to
Bypass mode. The cause of the fault should be checked and dealt
with before the UPS is turned on again by manual operation.
4)
Restore factory settings: all the settings can be recovered to default
factory settings. This can only be done in Bypass mode.