5
For model C500R-100-B, use minimum 10mm
2
for Equipment input
and grounding Wire, 75
C copper wire and 22.1 lb-in torque force
when connecting to input terminal block.
For model C500R-060-B, Use minimum 6mm
2
for Equipment input
and grounding Wire, 75
C copper wire and 18 lb-in torque force
when connecting to input terminal block.
For permanently connected equipment: make sure that a readily
accessible disconnect device is incorporated in the building
installation wiring.
To reduce the risk of fire, connect only to a circuit provided with
branch circuit overcurrent protection with an ampere rating in
accordance with the IEC/EN 60934 standard or your local electrical
code and have a contact air gap of at least 3 mm.
Uninterruptible power supply
output power
240V
C500R-060-B
40 amp
2-pole circuit breaker
C500R-100-B
63 amp
2-pole circuit breaker
You can connect four extended battery modules to the
uninterruptible power supply.
Before working on this circuit
- Isolate Uninterruptable Power System(UPS)
- Then check for Hazardous Voltage between all terminals
including the protective earth Risk of Voltage Backfeed.