Ep41
No pellets
Ep42
Mole or screw not working
Ep43
Communication error with
CMVAC
Ep45
Wood in firebox or
incorrect adjustment of
pellet side.
Ep46
Upper door opened -
wood side
Ep44
Boiler sensor error (pellet)
Boiler status:
Boiler work normally.
Possible causes:
Check the pellet level in the big
tank/room , check if the flexible tubes are blocked, check if
the turbine net is full with dust.
Boiler status:
Boiler work normally.
Possible causes:
Check the electric connections on the
mole/feeder screw, check the filthiness of the mole/feeder
screw.
Boiler status:
Boiler work normally.
Possible causes:
Check the UTP cable and its connections
with the electric boards.
Boiler status:
Boiler go to phases S7, C0 and OFF.
Possible causes:
Interruption on el. connections between
sensor and boiler, connection to the boiler, cold connection
or invalid sensor.
Boiler status:
Boiler go to phases S7, C0 and OFF.
Possible causes
:
Existing of larger quantity of wood in
firebox (wood side) during burner work (wood pellet side) or
incorrect adjustment of pellet side.
Boiler status:
Boiler go to phases S7, C0 and OFF.
Possible causes
:
Upper boiler door are opened (wood
side) during burner work (wood pellet side) after warning
time Wp15 expire, invalid microswitch - upper boiler door
(wood side).
Ep47
Screw refill
Boiler status:
Boiler work normally.
Possible causes
:
No pellets in CPSP-BP 800 tank for
refilling, problem with feeder screw in CPSP-BP 800,
interruption on el. connection between boiler and feeder
screw, connection to the boiler.
Error list
Technical instructions CONTROL UNIT
BioTec Plus
44