Important notes
•
Do not
mount the CT on the hot wire before you have already connected
the PAN-14 sensor securely to the CT!
•
If a PAN-14 sensor needs to be
replaced,
short circuit the CT’s outputs
to
each
other using a length of wire
before
PAN-14 is disconnected!
•
Do not
leave the CT mounted/installed on a hot wire without being short
circuited.
•
It is possible to have both the PAN-14 sensor and the short-circuiting wire
connected to the CT at the same time (but PAN-14 will not measure current
accurately while the short-circuiting wire is connected).
Registering the installed sensor
See
Panoramic Power deployment guide
Monitoring sensor activity
See
Panoramic Power deployment guide
Uninstalling a sensor
Open the sensor in the way you first opened it and remove it from the cable.