Revision 3.0 September 2019
© 2019 Centrica plc. Registered office: Millstream, Maidenhead Road, Windsor, Berkshire. SL4 5GD.
Registered in England & Wales No 3033654
9
PAN-14 Sensor installation guide
Sensor specifications
Physical dimensions
33.8 × 29 × 42.5 mm
1.33 × 1.14 × 1.67 inch
Current input range
(from external current transformer)
0-5 A
RMS
(up to 10 A peak)
Current measurement range
Any applicable range based on CT ratio
Current measurement accuracy
(typical, at 25° C)
<2% at I > 2% of full-scale current
Minimum operating current
(at input from external current
transformer)
0.03
–
0.05 A
AC frequency supported
50 Hz (EU, JPE)
60 Hz (US, JPW)
Transmission frequency
434 MHz (EU)
915 MHz (US)
923 MHz (JPE, JPW)
Transmission power (ERP)
0 dBm (max)
-4 dBm (max
–
JPE, JPW)
Transmission interval
10 seconds
Certification
USA and Canada
Safety: UL 61010-1, UL 61010-2-030, CAN/CSA-
C22.2 No. 61010-1 (ETL listed)
EMC: FCC Part 15 subpart B, ICES-003
Radio: FCC Part 15 subpart C, RSS-210, RSS-Gen
Europe
Safety: EN 61010-1, EN 61010-2-030 (CE)
EMC: EN ETSI 301 489-1, 301 489-3, 613 326-1
Radio: EN ETSI 300 220-1, 300 220-2
Australia
ACMA compliant
Russia
EAC compliant
Japan
Radio: ARIB STD-T108
CB Certification IEC 61010-1, IEC 61010-2-030
by Intertek Testing Services
Flammability rating of
external enclosure
UL94 V-0
Operating temperature
0
–
50° C
Storage temperature
-20
–
65° C