37
V10.19
1.
When the evaporator and condensing unit are located on the same level:
For
single evaporator systems
,
pipe the suction line with an inverted trap as shown to
prevent liquid migration to the compressor during the off cycle. For dual evaporator
system, install inverted suction traps on each evaporator to prevent liquid migration
between evaporators while running, and to prevent liquid migration to the compressor
during the off cycle. Pitch the
suction
line
slightly downward
to the condensing unit:
Summary of Contents for 3000Scmr
Page 1: ...V10 19 Control the Elements Split Ceiling Mount Refrigeration Systems Owner sManual...
Page 2: ...V10 19 This page intentionally left blank...
Page 7: ...7 V10 19 Evaporator Cut Sheets...
Page 8: ...8 V10 19 Condensing Unit Cut Sheets...
Page 13: ...13 V10 19 Evaporator Mounting Detail...
Page 20: ...20 V10 19...
Page 22: ...22 V10 19...
Page 23: ...23 V10 19 6000Scm Wiring Diagrams Option A Dual Power Valve Control Page 1 of 2...
Page 24: ...24 V10 19 6000Scm Wiring Diagrams Option A Dual Power Valve Control Page 2 of 2...
Page 25: ...25 V10 19 8000Scm Wiring Diagrams Option A Dual Power Valve Control Page 1 of 2...
Page 26: ...26 V10 19 8000Scm Wiring Diagrams Option A Dual Power Valve Control Page 2 of 2...
Page 28: ...28 V10 19 3000 4000Scm Wiring Diagram Option B Single Power Electronic Control...
Page 30: ...30 V10 19 6000Scm Wiring Diagram Option B Single Power Electronic Control Page 1 of 2...
Page 31: ...31 V10 19 6000Scm Wiring Diagram Option B Single Power Electronic Control Page 2 of 2...
Page 32: ...32 V10 19 8000Scm Wiring Diagram Option B Single Power Electronic Control Page 1 of 2...
Page 33: ...33 V10 19 8000Scm Wiring Diagram Option B Single Power Electronic Control Page 2 of 2...