Confirm the entire suction line from the evaporator unit to the condensing unit is insulated using cellular
insulation or equivalent. Seal all seams with Armaflex 520 Foam Insulation Adhesive or equivalent.
•
Confirm that the control is displaying the correct temperature and that no alarms are present.
INSTALLING THE CONDENSING UNIT(continued)
Finalizing the Installation
Approximate Operating Pressures
(Cellar temperature 55°F)
Low Side PSI
High Side PSI
Temp.
60°F
75°F
85°F
95°F
30-35 PSIG
32-37 PSIG
110-115 PSIG
33-38 PSIG
130-135 PSIG
156-161 PSIG
34-39 PSIG
82-87 PSIG
Page 46