![Cegasa eBick MCP Series User Manual Download Page 7](http://html1.mh-extra.com/html/cegasa/ebick-mcp-series/ebick-mcp-series_user-manual_2578986007.webp)
www.cegasa.com Page -5-
User Manual R10
–
First steps
–
2 Technical characteristics of eBick system
Module MCP (Control and protections) MCP SERIEs
MCP PARALLELs
Chemistry
LiFePO4 (LFP)
LiFePO4 (LFP)
Rated voltage [V]
Depending on the number
of modules connected in
series
(consult CEGASA)
48
Voltage range [V]
41 - 52,5
Capacity [Ah]
180
Depending on the
number of modules
connected
Energy [KWh]
Depending on the number of modules connected
I MAX charge continuous [A]
180
250
I MAX discharge continuous [A]
180
250
I MAX discharge pulse (seg.) [A]
360 (15seg)
360 (30seg)
Rated power continuous [KW]
Depending on the number
of modules connected in
series
12KW
Rated power pulse [KW]
17KW
Number of cycles
> 6000 (70% DoD)
> 5000 (80% DoD)
> 4000 (90% DoD)
Temperature range in (ºC) Charge
From 0 to +50ºC
Temperature range in (ºC) Discharge
From -20 to +60ºC
Storage temperature (ºC)
From -20 to +45ºC
Storage temperature recommended (ºC)
From 15 to +25ºC
Power connector
Anderson SB175 (Wire
section 50mm2)
Anderson SB350 (Wire
section 70mm2)
Dimensions (L x P x A, mm)
Depending on the number of modules connected
Weight (Kg)
Depending on the number of modules connected
Degree of envelope protection
IP 30
Table 1.