![Cegasa eBick MCP Series User Manual Download Page 39](http://html1.mh-extra.com/html/cegasa/ebick-mcp-series/ebick-mcp-series_user-manual_2578986039.webp)
www.cegasa.com Page -37-
User Manual R10
–
First steps
–
8.2.2 MCP Parallels
Charging current by SOF
SOC
Charging current
1. 0-94%
250A x Temperature
coefficient
2. 95-99%
20A x Number of modules in parallel x Temperature
coefficient
3. 100%
0A x Temperature
coefficient
Temperature
range in
CHARGE (ºC)
Temperature
coefficient
0-5
0,2
6-11
0,5
11-45
1
46-50
0,2
Charging voltage by SOF
Temperature
range in
CHARGE
(ºC)
Charging voltage
(V)
0-5
51,2
6-11
51,5
11-45
51,9
46-50
51,2
8.3 Discharging
In the discharging process, the maximum current demanded by the application is
guaranteed at all times, provided that the value does not exceed that of the alarms of the
eBick system in continuous and pulse mode (see point 2).
The minimum voltage that cannot be lowered in the discharge is sent to the inverter to
ensure battery operation. This value is:
Vmin = 42V x Number modules connected in series
8.4 Equalizing
Equalization process in the eBick family is
passive
and is governed by the MCP only.
The system enters in equalization mode when the voltage dispersion within the system
exceeds
40mV
. The equipment goes out to equalize when the voltage dispersion
reaches a value of
10mV
or when one of the series reaches the limit value of
3340mV
.
Summary of Contents for eBick MCP Series