![CE+T Power e-one 10 - 48/230 User Manual Download Page 9](http://html1.mh-extra.com/html/ce-t-power/e-one-10-48-230/e-one-10-48-230_user-manual_2577179009.webp)
Description
9
– e-one 10 - 48/230 - User manual - v1.2
DC Input Specifications
Nominal voltage (DC)
48 V
Voltage range (DC)
40 - 60 V
Nominal current at 800 W / 48 VDC
19 A
Maximum input current (for 15 seconds) /
voltage ripple
28 A / 2 mV psopho @ 48 V - 80% LOAD
AC Input Specifications
Nominal voltage (AC)
230 V
Nominal frequency
Separate part number for 50 Hz and 60 Hz
Voltage range
207 - 253 Vac
Frequency range
50 Hz (range 47 – 53 Hz) / 60 Hz (range 57 – 63 Hz)
AC Output Specifications*
Nominal voltage (AC)
230 V
Frequency / frequency accuracy
Separate part number for 50 Hz / ± 0.1% and 60 Hz / ± 0.1%
Total harmonic distortion (resistive load)
< 3 %
Turn on delay
20 s
Nominal current. Protected against reverse current
4.35 A at 230 VAC
Crest factor at nominal power
2.5 : 1
With short circuit management and protection
> 9A (2xIn) for 15 s and then no output power from module
Transfer time from DC mode to By-pass mode and
vice-versa
< 10 ms
Signaling & Supervision
Display
Front LED
Alarms output / supervision
Dry contact on the front
Remote ON / OFF
On the front
Standard Compliances
Standards
IEC60950
ETS 300 386 – 2 : 2mV
EN 55022 Class A Radiated and Conducted
ETS 300 132 – 2 : Product Standard
IEC 61000-3-2 harmonic current class A
EN61000-4-2 ESD criteria A - 15 kV Air and 8 kV contact
EN61000-4-3 RF Field – Enclosure Port criteria A : 10 V/m
EN61000-4-4 Burst - All ports criteria A : 2kV
EN61000-4-5 Surge criteria B all ports
EN61000-4-6 class A criteria A 10V
* This specification is valid for DC mode only. In By-pass mode, the output will be same as AC input.