Step B:
Place the e-one module on the wall and fix with the screws.
5.4 Wiring
The insulation cover of conductors must meet the local and international standards and the cross section must be
related to the upstream protections.
Caution:
The e-one has internal fuses on DC input.
Those device do not protect the upstream cables connected to DC and AC inputs and
upstream breakers or fuses shall be set up in accordance with DC and AC wires ratings, to
meet the local national electrical code standard.
All breakers, cables and wires should be classified for min 90°C (194°F) operation. Matching
respectively Line / Neutral feeder to Line / neutral input connections is required.
Before any intervention on the e-one input, operator has to make sure that power is switched
off on DC leads and AC input mains.
Some safety labels are stuck on the unit. It should not be removed.