6. Getting started
6.1 Starting procedure
1. Check the DC and AC power supply (within range).
2. Turn on the DC breaker to the module. (Wait at least 30 seconds until INFO LED turns solid green)
3. Check AC output voltage at IEC socket
4. Apply the AC input power to the module (For Bypass)
6.2 LED and Lamp status
e-one 10 - 48/230 module indicate its functional status
through module front
INFO
LED and
AC OUT
Lamp.
6.2.1 LED Indications - Alarm status
There is one LED at front for input and output status
S. NO
INFO LED
Description
Alarm
1
OFF
No inverter output
2
Permanent GREEN
Inverter working fine
-
3
Fast - Blinking GREEN
DC source is out of range
4
Blinking ORANGE
Output Power / VA Derating / Temperature Derating
-
5
Slow - Blinking RED
Inverter output short-circuited
-
6
Fast - Blinking RED
Module over-temperature and output OFF
7
Permanent RED
Inverter output OFF due to permanent short-circuit
8
Blinking RED - ORANGE
Inverter output voltage is out of range
-
9
Blinking RED - GREEN
Inverter output OFF (Load transfer to BYPASS)
Due to Load power too High
10
Slow - Blinking GREEN
AC Input - Unavailable / Out-of-range
-
11
Permanent ORANGE
Inverter overloaded output unavailable
(Load transfer to BYPASS)
6.2.2 Lamp Status
S. NO
AC OUT Lamp
Description
1
ON
Voltage present at output terminal
2
OFF
Voltage is not present at output terminal
LED
Lamp
INFO
AC OUT
Getting started
18