5.4.4.2 Remote ON/OFF
e-one 10 - 48/230 system can be remotely activated or stopped (stand-by mode).
Changeover contacts must be used.
To turn off the Inverter remotely, both conditions “Pin 1-3, Closed” and “Pin 2-3, Open” must be
met.
The voltage present on terminal 1 and 3 is +5 V (galvanically insulated). Care should be taken to avoid connecting any
external voltage on terminal 1 to 3. Maximum wire size is 1 mm²
Functional table for remote ON/OFF function
States
Pin 1-3
Pin 2-3
System status
1
Open
Open
System working normally
2
Closed
Open
Output switched OFF
LED OFF
3
Open
Closed
System working normally
4
Closed
Closed
System working normally
The 3 wires must be used for the redundancy on the remote ON/OFF. Use NO/NC relay contact.
Warning: If remote ON/OFF is not used, pin 2 and 3 MUST be bridged together!