Brownout
800 W @ 150 Vac / 1000 W @ >190 Vac linear
decreasing
Power factor / THD
> 99% / < 3%
Frequency range (selectable) / synchronization range
50 Hz (range 47 – 53 Hz) / 60 Hz (range 57 – 63 Hz)
DC Input Data
DC voltage: Nominal / range
48 VDC / (40-60V)*
Nominal current (at 48 Vdc and 1000 W output)
22.3 A
Maximum input current (at 48 Vdc for 15 second) /
voltage ripple
34 A / < 10 mV RMS
AC Output Data
Efficiency (Typical): Enhanced power conversion / on line
96% / >92.5%
Nominal voltage AC** Adjustable)
230 V (200 - 240 VAC)
Frequency / frequency accuracy
50 or 60 Hz / 0.03%
Nominal Output power
1250 VA / 1000 W
Short time overload capacity
150% (15 seconds)
Admissible load power factor
Full power rating from 0 inductive to 0 capacitive
Total harmonic distortion (resistive load)
< 3%
Load impact recovery time (10% - 90%)
≤ 0.4 ms
Nominal current
5.4 A @ 230 Vac
Crest factor at nominal power
3 : 1 for load P.F. ≤ 0.7
Short circuit clear up capacity 0 - 20 ms
21.7 A for 20 ms
Short circuit current after > 15 ms - 15 s
8.1 A for 1 minute
AC output voltage stability
±1% from 10% to 100% load
In Transfer Performance
Max. voltage interruption / total transient voltage
duration (max)
0 s / 0 s
Signalling & Supervision
Display
Synoptic LED
Supervision
Inview ranges / Inview S - T302004100, Inview S Slot -
T602004110, Inview GW - T602004000
Remote on / off
On rear terminal of the shelf
Alarms output
2 dry contacts and 2 digital inputs
Safety & EMC
Safety
EN62040-1
EMC
EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN
61000-4-5 / EN 61000-4-6 / EN 61000-4-8
ETSI EN 300386 v1.9.1
* Permanent 1000 W / derating apply based on internal heatsink T°.
** Operation within lower voltage networks leads to de-rating of power performances.