2019 CDI Meters, Inc.
10.19
R
EMOTE
D
ISPLAY
If you are using the summing remote display (SRD), connect the three terminals
marked “display” to the corresponding terminals in the remote display. The meter
may be powered from the remote display if the cable is 22 gauge or heavier and
the distance is no greater than 200 feet. CDI 5100 flowmeters require summing
remote displays with Rev. 24 or later firmware.
M
ILLIAMP
O
UTPUT
The 4 - 20 milliamp output is optically isolated within the meter and it is provided
with a factory-installed jumper which allows it to source a milliamp signal
powered from the meter. The resistance of the loop connected to the output
should not exceed 600 Ohms.