REVEX
1PH from 30A to 40A
User’s manual
51
Firing type
Choose a correct firing type allows to optimize the thyristor unit for the installed load.
The firing type has already configured in line with customer requirements that are defined in the Order Code.
The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel.
Caution:
this procedure must be performed only by qualified persons.
11.1 Zero Crossing
ZC firing mode is used with Logic
Output from temperature controllers
and the Thyristor operates like a
contactor.
The Cycle time is performed by
temperature controller. ZC minimizes
interferences because the Thyristor
unit switches ON-OFF at zero voltage.
11.2 Single Cycle
Single Cycle it’s the faster zero crossing
switching method in relationship of the
power demand from a temperature
regulator or from an external signal.
With input signal at 25% the output is
one cycle ON and three cycles OFF.
With input signal at 50% the output is
one cycle ON and one cycle OFF.
With input signal at 75% the output is
three cycles ON and one cycle OFF.
With input signal at 76% the output is
the same of 75% but for each ON cycle
the microprocessor divides 76/75, and
when the sum of rests is one, the unit
does one more cycle ON. For this firing is necessary to have analog input.
The Single Cycle is used to control the loads with low inertia or for infrared lamps to short wave.
11.3 Burst Firing
The Burst Firing is similar to the Single
Cycle, but consecutive cycles ON
are selectable between 1 and 255,
with input signal equal at 50%. When
is specified 1 the firing type is Single
Cycle.
Burst Firing is a method zero crossing
that it reduces the electromagnetic
interferences because the thyristor
switches at zero voltage crossing.
The example show the Burst Firing
with Burst cycles=4.
ON
OFF
Voltage Supply (V)
Load Voltage (V)
SSR from controller
25%
50%
75%
100%
ON
OFF
Voltage Supply (V)
Load Voltage (V)
25%
50%
75%
100%
ON
OFF
Voltage Supply (V)
Load Voltage (V)
11