30
REVEX
1PH from 30A to 40A
User’s manual
9.4.2 Setup Menu
This section describes each item on the setup menu. Use this menu to configure the power controller for the
load.
The password to access this menu is 2.
Parameter Name
Description
Range
Unit
Modbus
Address
Par.
Type
Out Scale
Set the percentage by which the set point is
scaled. For example, if a 0 to 10V analog input
providing the set point is 5V and output scaling is
80% then the effective set point is 40%
0 to 100.0
%
16
Read
Write
Parameter Name
Description
Default
Range
Unit
Modbus
Address
Par.
Type
I Limit SP
Set the maximum percent of the
nominal current that the power control
allows. This parameter indicates RMS
current by default.
When parameter 52 is set to 1, this
parameter indicates peak current
100%
0 to 100.0
%
17
Read
Write
Nom Line V
Set the nominal value for the line
voltage input
220V
0 to 1023
V
37
Read
Write
Nominal I
Set the nominal load current
Maximum
current
0 to 999.9
A
38
Read
Write
Soft Start
Set the duration of the soft start in
increment of 100mSec. The power
controller ramps set to point changes
over the time set here. For more
information see “Firing type” page:
Soft Start with Burst Firing and Soft
Start with Phase Angle
100
(10 sec)
0 to 255
(0 to 25,5
sec)
23
Read
Write
SP select
Choose the source for the remote set
point
0
61
Read
Write
Option
Value
Analog In 1
0
Analog In 2
1
100
80
60
40
20
0
0 20 40 60 80 100
Input
Output Scaling = 100%
Output Scaling = 80%
Output Scaling = 40%
Scaled Set P
oint
Summary of Contents for REVEX 1Ph 30A
Page 2: ......