34
REVEX
1PH from 30A to 40A
User’s manual
9.4.4 Hardware Menu
This section describes each item on the hardware menu. Use this menu to configure how the inputs and
outputs are used in the application.
The password to access this menu is 5.
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Analog In 1
Choose the type of signal to be measured by
analog input 1
1
44
Read
Write
Option
Description
Value
0-10V
0 to 10 Vdc or 10,000Ω
1
4-20mA
4 to 20 mAdc
2
0-20mA
0 to 20 mAdc
3
DEFAULT:
0-10V
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
Analog In 2
Choose the type of signal to be measured by
analog input 2
1
105
Read
Write
Option
Description
Value
0-10V
0 to 10 Vdc or 10,000Ω
1
4-20mA
4 to 20 mAdc
2
0-20mA
0 to 20 mAdc
3
DEFAULT:
0-10V
1
Parameter Name
Description
Default
Modbus
Address
Par.
Type
An2 Funct
Choose how the signal measured by analog input
2 is used
0
116
Read
Write
Option
Description
Value
I Limit SP
Current Limit Set point
0
Feedback
External feed-back
1
Set Point
Power Demand set point
2
DEFAULT 1Phase:
I Limit
0