CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
32
11.3.3
Secondary input (Terminals 12 & A1- see par. 7.4)
This analogue input 0-10V may be configured for External current limit profiling.
The Secondary input is already configured in line with customer requirements that are defined in the
complete product code. The product code is written on the identification label.
However, if you wish to change the input type proceed as follows:
Warning:
this procedure can be done just by specialized personnel
Front PCB
J2
A
B
C
J1
A
B
C
To configure the input type, set the jumper as below represented:
Current Limit
J2
J1
Regulation through the R13 trimmer, mounted on the
front PCB. (secondary input not used)
C-B C-B
Regulation through the secondary input
(External current limit profiling)
B-A C-B
If the user change the type of Secondary input, it’s necessary repeat the calibration procedure
(see par. 9.3)
11.4
Digital Input
CD3200 thyristor unit has two digital inputs.