CD Automation srl
CD3200-1PH from 15A to 110A
User’s Manual
22
8
Power output features
Current
Voltage
range
Repetitive peak
reverse voltage
Latching
current
Max peak
one cycle
Leakage
current
I
2
T value
max
Frequency
range
Power loss
Isolation
Voltage
(A)
(V)
(480V)
(600V)
(mAeff)
(10msec.)
(A)
(mAeff)
tp=10msec
(Hz)
I=Inom (W)
Vac
15A 24÷480
1200
1200
150
230
15
610
47÷70
18
2500
25A 24÷480
1200
1200
150
230
15
610
47÷70
30
2500
35A 24÷600
1200
1600
250
400
15
780
47÷70
42
2500
45A
24÷600
1200
1600
250 600 15 1800
47÷70 54 2500
60A
24÷600
1200
1600
450 1000 15 4750
47÷70 72 2500
90A 24÷600
1200
1600
450
2000
15
19100 47÷70
108
2500
110A 24÷600
1200
1600
450
1540
15
11300 47÷70
137
2500
8.1
Derating curve
1
0.8
0.6
0.4
0.2
0
40
50
60
70
80
K
°C
I = I x K
NOM
MAX
8.2
Cooling fans
The thyristor units from size 110A are equipped with a cooling fan. The supply voltage is standard
230VAC
±
15% 50/60Hz or optional 110VAC
±
15% 50/60Hz.
The fan’s power consumption is below listed:
Size
Number of fans
C
US
LISTED
UL
®
Number of fans
110A (S8C)
One Fan - 16W
One Fan - 16W