Appendices
Installation, Operation & Maintenance of the Wireless Sensing Family
43
B.4.5:
Check connectivity with lancusrouter
In case the USG is configured properly and still fails to connect the
lancusrouter, use laptop’ terminal to connect . Most terminal software will
do the job . The ZOC terminal will be used to demonstrate connectivity
test. The screenshot below presents testing to the lancusrouter of the
development server. IP 78.47.220.154 port 3901 .
Figure 22: Terminal connection test with lancusrouter
Press connect and when the status bar indicates connection, press Z
character. This indicates the lancusrouter to enter echo mode in which it
returns any received character.
If this process fails the problem relates to firewall policy
which should be handled by the hosting company’s IT.
When this problem is resolved, the connectivity problem will be also be
resolved.