Programming specific applications
ZS Sensor
CARRIER CORPORATION ©2020
Applications Guide
All rights reserved
25
When a user presses the
button, the screen initially shows the current zone HVAC mode. With each press of
the button, the display shows one of the following options:
Auto
The control program determines the mode.
Heating only
Cooling only
Fan only
ZS Pro: To program manual HVAC control (fan only, cooling only, or heating only) using the or
button
1
From the
Sys In
microblock menu, add a
BACnet Multi-State Value Parameter
microblock.
2
On the Property Editor's
Rnet
tab, check
Enable Rnet
.
3
Select the
Zone Mode Request (601)
from the
Rnet Tag
drop-down list.
4
Check
Editable
.
5
Select
Show on
the
Information Screen
or
Diagnostics Screen
.
6
On the
Properties
tab in the
Rnet Text
fields, type the text that you want a sensor to show for each mode.
NOTES
○
The letters K, M, Q, W, X do not display on a screen.
○
If you do not enter text, the sensor will show the Value number for the mode.
When a user goes to the information screen, it will initially show the current mode. The user taps the or
button to cycle through the mode options.
Summary of Contents for ZS