Programming specific applications
ZS Sensor
CARRIER CORPORATION ©2020
Applications Guide
All rights reserved
26
Hospitality Mode
Hospitality mode is typically used for hotel/motel rooms. The Home screen always displays the active effective
setpoint or the average of the heating and cooling setpoints if the mode is auto. The effective setpoint is
adjustable. The sensor also displays any active status icons.
To use this mode, select
Hospitality mode
on the
Rnet
tab of the BACnet Setpoint microblock.
Clean room application
This application requires two display sensors, one inside the clean room and one on the outside. While both
sensors have temperature sensing ability, only the temperature on the inside of the clean room should be used for
control. Both sensors should display the sensed temperature on the inside of the clean room.
You set up this scenario in the Sensor Binder microblock and the ASVI microblock for Zone Temp.
1
Define the 2 sensors in the Sensor Binder microblock.
2
In the Zone Temp ASVI microblock:
a)
Check
Enable
for the first sensor (Index 1). Only that sensor's temperature value will be used.
b)
Set
Show on sensors
to
Calculated Value
.