![Carrier WeatherMaker 50KCQ A04 Series Service And Maintenance Instructions Download Page 65](http://html.mh-extra.com/html/carrier/weathermaker-50kcq-a04-series/weathermaker-50kcq-a04-series_service-and-maintenance-instructions_2560323065.webp)
65
Italics
indicates field-supplied drive is re
q
uired.
1. Recommend using field-supplied motor (HD5
8
FE651 for 230-v and
460-v, HD5
8
FE576 for 575-v), fan pulley (part number
KR11AZ606), motor pulley (part number KR11HY213), and belt
(part number KR29AF043).
Italics
indicates field-supplied drive is re
q
uired.
1. Recommend using field-supplied motor (HD5
8
FE651 for 230-v and
460-v, HD5
8
FE576 for 575-v), fan pulley (part number
KR11AD561), motor pulley (part number KR11HY1
8
4), and belt
(part number KR29AF041).
Table K — 50KCQ A05 - 4 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
630
0.20
755
0.31
859
0.43
949
0.56
1030
0.70
1300
659
0.24
781
0.36
883
0.48
972
0.61
1052
0.76
1400
689
0.28
808
0.40
908
0.53
995
0.67
1075
0.82
1500
720
0.33
836
0.46
933
0.59
1020
0.74
1098
0.89
1600
752
0.38
864
0.52
960
0.66
1044
0.81
1121
0.97
1700
784
0.44
893
0.58
986
0.73
1070
0.89
1146
1.05
1800
816
0.50
922
0.65
1014
0.81
1096
0.97
1171
1.14
1900
849
0.58
952
0.73
1042
0.90
1122
1.07
1196
1.24
2000
882
0.66
982
0.82
1070
0.99
1149
1.17
1222
1.35
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
1104
0.84
1173
0.99
1237
1.15
1298
1.32
1356
1.49
1300
1125
0.91
1194
1.06
1258
1.23
1318
1.40
1375
1.58
1400
1147
0.98
1215
1.14
1278
1.31
1338
1.48
1395
1.67
1500
1170
1.05
1237
1.22
1299
1.39
1359
1.57
1416
1.76
1600
1193
1.13
1259
1.31
1321
1.49
1380
1.67
1437
1.86
1700
1216
1.22
1282
1.40
1344
1.59
1402
1.78
1458
1.97
1800
1240
1.32
1305
1.50
1366
1.69
1424
1.89
1480
2.09
1900
1265
1.43
1329
1.61
1390
1.81
1447
2.01
1502
2.22
2000
1290
1.54
1353
1.73
1413
1.93
1470
2.14
1525
2.35
Medium static 920-1303 RPM, 1.5 HP
High static 1035-1466 RPM, 2.0 BHP max
Table L — 50KCQ A05 - 4 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
682
0.25
800
0.36
897
0.48
982
0.61
1058
0.75
1300
717
0.29
832
0.42
928
0.55
1011
0.68
1086
0.82
1400
753
0.34
865
0.48
958
0.61
1041
0.76
1115
0.91
1500
789
0.40
898
0.54
990
0.69
1071
0.84
1144
1.00
1600
826
0.47
932
0.62
1022
0.77
1102
0.93
1174
1.09
1700
863
0.54
966
0.70
1055
0.86
1133
1.03
1205
1.20
1800
901
0.62
1001
0.79
1088
0.96
1165
1.13
1235
1.31
1900
939
0.71
1037
0.89
1121
1.07
1197
1.25
1267
1.44
2000
978
0.81
1073
0.99
1156
1.18
1230
1.37
1299
1.57
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1200
1128
0.89
1192
1.03
1252
1.18
1309
1.34
1363
1.50
1300
1155
0.97
1219
1.12
1279
1.28
1336
1.44
1389
1.61
1400
1183
1.06
1247
1.22
1306
1.38
1362
1.55
1416
1.72
1500
1212
1.16
1275
1.32
1334
1.49
1389
1.67
1443
1.85
1600
1241
1.26
1303
1.43
1362
1.61
1417
1.79
1470
1.98
1700
1271
1.37
1332
1.55
1390
1.74
1445
1.93
1498
2.12
1800
1301
1.50
1362
1.68
1419
1.87
1474
2.07
1526
2.27
1900
1331
1.63
1392
1.82
1449
2.02
1503
2.22
—
—
2000
1362
1.77
1422
1.97
1478
2.18
1532
2.38
—
—
Medium static 920-1303 RPM, 1.5 HP
High static 1035-1466 RPM, 2.0 BHP max
APPENDIX C — FAN PERFORMANCE
Summary of Contents for WeatherMaker 50KCQ A04 Series
Page 34: ...34 Fig 53 RTU Open Overlay for Economizer Wiring ...
Page 35: ...35 Fig 54 VFD Overlay for W2770 Controller Wiring ...
Page 70: ...70 Fig C 50KCQ A04 A05 A06 Control Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 71: ...71 Fig D 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 72: ...72 Fig E 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 73: ...73 Fig F 50KCQ A04 A05 A06 Power Wiring Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 74: ...74 Fig G 50KCQ A04 A05 A06 Power Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 75: ...75 Fig H 50KCQ Premier Link Control Diagram APPENDIX D WIRING DIAGRAMS ...
Page 76: ...76 Fig I 50KCQ RTU Open Control Diagram APPENDIX D WIRING DIAGRAMS ...