![Carrier WeatherMaker 50KCQ A04 Series Service And Maintenance Instructions Download Page 19](http://html.mh-extra.com/html/carrier/weathermaker-50kcq-a04-series/weathermaker-50kcq-a04-series_service-and-maintenance-instructions_2560323019.webp)
19
Table 6 — Heating and Cooling Troubleshooting
PROBLEM
CAUSE
REMEDY
Compressor and
outdoor fan will
not start
Power failure.
Call power company.
Fuse blown or circuit breaker tripped.
Replace fuse or reset circuit breaker. Determine root cause.
Defective thermostat, contactor, transformer, control
relay, or capacitor.
Replace component.
Insufficient line voltage.
Determine cause and correct.
Incorrect or faulty wiring.
Check wiring diagram and rewire correctly.
Thermostat setting too high.
Lower thermostat setting below room temperature.
High pressure switch tripped.
See problem “Excessive head pressure”.
Low pressure switch tripped.
Check system for leaks. Repair as necessary.
Freeze-up protection thermostat tripped.
See problem “Suction pressure too low”.
Compressor will
not start
but outdoor fan
runs
Faulty wiring or loose connections in compressor
circuit.
Check wiring and repair or replace.
Compressor motor burned out, seized, or internal
overload open.
Determine cause. Replace compressor or allow enough time for internal
overload to cool and reset.
Defective run/start capacitor, overload, start relay.
Determine cause and replace compressor.
One leg of 3-phase power dead.
Replace fuse or reset circuit breaker. Determine cause.
Compressor
cycles (other
than normally
satisfying
thermostat)
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and recharge to nameplate.
Defective compressor.
Replace and determine cause.
Insufficient line voltage.
Determine cause and correct.
Blocked outdoor coil or dirty air filter.
Determine cause and correct.
Defective run/start capacitor, overload, or start relay. Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty outdoor-fan (cooling) or indoor-fan (heating)
motor or capacitor.
Replace.
Restriction in refrigerant system.
Locate restriction and remove.
Compressor
operates
continuously
Dirty air filter.
Replace filter.
Unit undersized for load.
Decrease load or increase unit size.
Thermostat set too low (cooling).
Reset thermostat.
Low refrigerant charge.
Locate leak; repair and recharge.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Outdoor coil dirty or restricted.
Clean coil or remove restriction.
Compressor
makes
excessive noise
Compressor rotating in the wrong direction.
Reverse the 3-phase power leads as described in Start-Up (page 55).
Excessive head
pressure
Dirty outside air or return air filter (heating).
Replace filter.
Dirty outdoor coil (cooling).
Clean coil.
Refrigerant overcharged.
Recover excess refrigerant.
Air in system.
Recover refrigerant, evacuate system, and recharge.
Condensing air restricted or air short-cycling.
Determine cause and correct.
Head pressure
too low
Low refrigerant charge.
Check for leaks; repair and recharge.
Compressor scroll plates defective.
Replace compressor.
Restriction in liquid tube.
Remove restriction.
Excessive suction
pressure
High heat load.
Check for source and eliminate.
Compressor scroll plates defective.
Replace compressor.
Refrigerant overcharged.
Recover excess refrigerant.
Suction
pressure
too low
Dirty air filter (cooling).
Replace filter.
Dirty or heavily iced outdoor coil (heating).
Clean outdoor coil. Check defrost cycle operation.
Low refrigerant charge.
Check for leaks; repair and recharge.
Metering device or low side restricted.
Remove source of restriction.
Insufficient indoor airflow (cooling mode).
Increase air quantity. Check filter and replace if necessary.
Temperature too low in conditioned area.
Reset thermostat.
Field-installed filter drier restricted.
Replace.
Outdoor ambient below 25°F (cooling).
Install low-ambient kit.
Outdoor fan motor(s) not operating (heating).
Check fan motor operation.
Summary of Contents for WeatherMaker 50KCQ A04 Series
Page 34: ...34 Fig 53 RTU Open Overlay for Economizer Wiring ...
Page 35: ...35 Fig 54 VFD Overlay for W2770 Controller Wiring ...
Page 70: ...70 Fig C 50KCQ A04 A05 A06 Control Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 71: ...71 Fig D 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 72: ...72 Fig E 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 73: ...73 Fig F 50KCQ A04 A05 A06 Power Wiring Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 74: ...74 Fig G 50KCQ A04 A05 A06 Power Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 75: ...75 Fig H 50KCQ Premier Link Control Diagram APPENDIX D WIRING DIAGRAMS ...
Page 76: ...76 Fig I 50KCQ RTU Open Control Diagram APPENDIX D WIRING DIAGRAMS ...