37
*
For single enthalpy control, the module compares outdoor enthalpy to
the ABCD set point.
† Power at N terminal determines Occupied/Unoccupied setting: 24 vac
(Occupied), no power (Unoccupied).
**
Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
***
Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
Fig. 57 — EconoMi$er IV Functional View
EconoMi$er IV
Table 13 provides a summary of EconoMi$er IV logic. Trou-
bleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 57. Typi-
cal settings, sensor ranges, and jumper positions are also shown.
An EconoMi$er IV simulator program is available from Carrier
to help with EconoMi$er IV training and troubleshooting.
ECONOMI$ER IV STANDARD SENSORS
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is fac-
tory-installed on the EconoMi$er IV in the outdoor airstream.
(See Fig. 58.) The operating range of temperature measure-
ment is 40°F to 100°F (4°C to 38°C). See Fig. 60.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor located at
the inlet of the indoor fan. (See Fig. 58.) This sensor is factory
installed. The operating range of temperature measurement is
0° to 158°F (–18°C to 70°C). See Table 14 for sensor tempera-
ture and resistance values.
Table 13 — EconoMi$er IV Input/Output Logic
INPUTS
OUTPUTS
Demand
Controlled
Ventilation (DCV)
Enthalpy*
Y1 Y2
Compressor
N Terminal†
Outdoor
Return
Stage 1 Stage 2
Occupied
Unoccupied
Damper
Below set
(DCV LED off)
High (Free
Cooling LED off)
Low
On On
On
On
Minimum position
Closed
On Off
On
Off
Off Off
Off
Off
Low (Free
Cooling LED on)
High
On On
On
Off
Modulating** (between min.
position and full-open)
Modulating** (between closed
and full-open)
On Off
Off
Off
Off Off
Off
Off
Minimum position
Closed
Above set
(DCV LED on)
High (Free
Cooling LED off)
Low
On On
On
On
Modulating†† (between min.
position and DCV maximum)
Modulating†† (between closed
and DCV maximum)
On Off
On
Off
Off Off
Off
Off
Low (Free
Cooling LED on)
High
On On
On
Off
Modulating***
Modulating†††
On Off
Off
Off
Off Off
Off
Off
Summary of Contents for WeatherMaker 50KCQ A04 Series
Page 34: ...34 Fig 53 RTU Open Overlay for Economizer Wiring ...
Page 35: ...35 Fig 54 VFD Overlay for W2770 Controller Wiring ...
Page 70: ...70 Fig C 50KCQ A04 A05 A06 Control Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 71: ...71 Fig D 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 72: ...72 Fig E 50KCQ A04 A05 A06 Power Wiring Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 73: ...73 Fig F 50KCQ A04 A05 A06 Power Wiring Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 74: ...74 Fig G 50KCQ A04 A05 A06 Power Wiring Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 75: ...75 Fig H 50KCQ Premier Link Control Diagram APPENDIX D WIRING DIAGRAMS ...
Page 76: ...76 Fig I 50KCQ RTU Open Control Diagram APPENDIX D WIRING DIAGRAMS ...