92
APPENDIX III. FAN PERFORMANCE (cont.)
48TC**06
1 Phase
5 Ton Horizontal Supply
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1500
800
0.39
904
0.49
999
0.60
1087
0.72
1169
0.85
1625
849
0.48
947
0.59
1038
0.70
1122
0.83
1201
0.96
1750
899
0.59
992
0.70
1078
0.82
1159
0.95
1235
1.08
1875
950
0.70
1038
0.82
1120
0.95
1198
1.08
1271
1.22
2000
1001
0.84
1085
0.96
1163
1.09
1238
1.23
1309
1.38
2125
1053
0.99
1133
1.12
1208
1.26
1280
1.40
---
---
2250
1106
1.16
1182
1.29
1254
1.44
---
---
---
---
2375
1159
1.34
1231
1.49
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1247
0.98
1320
1.13
1390
1.28
1457
1.44
---
---
1625
1276
1.10
1348
1.24
1416
1.40
---
---
---
---
1750
1308
1.22
1377
1.38
---
---
---
---
---
---
1875
1342
1.37
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 87.
Boldface
indicates field---supplied drive is required.
48TC**06
1 Phase
5 Ton Vertical Supply
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1500
848
0.42
968
0.55
1069
0.68
1158
0.80
1238
0.94
1625
897
0.51
1013
0.65
1111
0.79
1198
0.93
1277
1.07
1750
947
0.61
1059
0.76
1155
0.91
1240
1.06
1318
1.21
1875
997
0.72
1105
0.89
1199
1.05
1283
1.21
1359
1.37
2000
1048
0.85
1153
1.03
1244
1.20
1326
1.37
---
---
2125
1100
1.00
1201
1.19
1290
1.37
---
---
---
---
2250
1152
1.16
1250
1.36
---
---
---
---
---
---
2375
1205
1.34
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1500
1312
1.07
1380
1.20
1445
1.34
1506
1.48
---
---
1625
1350
1.21
1418
1.35
1482
1.50
---
---
---
---
1750
1390
1.36
---
---
---
---
---
---
---
---
1875
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 87.
Boldface
indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).
48TC
Summary of Contents for WeatherMaker 48TC*A04
Page 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Page 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Page 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Page 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Page 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...
Page 65: ...65 C08317 Fig 84 48TC Unit Wiring Diagram Control A06 48TC ...