![Carrier WeatherMaker 48TC*A04 Service And Maintenance Instructions Download Page 27](http://html.mh-extra.com/html/carrier/weathermaker-48tc-a04/weathermaker-48tc-a04_service-and-maintenance-instructions_2560316027.webp)
27
125,000/90,000 BTUH INPUT
180,000/120,000 BTUH INPUT
240,000/180,000 BTUH INPUT
250,000/200,000 BTUH INPUT
C08447
Fig. 36 -- Spark Adjustment (08--12)
Table 8 – LED Error Code Description*
LED INDICATION
ERROR CODE
DESCRIPTION
ON
Normal Operation
OFF
Hardware Failure
1 Flash
{
Evaporator Fan On/Off Delay Modified
2 Flashes
Limit Switch Fault
3 Flashes
Flame Sense Fault
4 Flashes
4 Consecutive Limit Switch Faults
5 Flashes
Ignition Lockout Fault
6 Flashes
Induced---Draft Motor Fault
7 Flashes
Rollout Switch Fault
8 Flashes
Internal Control Fault
9 Flashes
Software Lockout
LEGEND
LED
--- Light Emitting Diode
* A 3---second pause exists between LED error code flashes. If
.
more than one error code exists, all applicable codes will be
displayed in numerical sequence.
{
Indicates a code that is not an error. The unit will continue to
operate when this code is displayed.
IMPORTANT
: Refer to Troubleshooting Table 13 and
Table 14 for additional information.
Orifice Replacement
This unit uses orifice type LH32RFnnn (where nnn
indicates orifice reference size). When replacing unit
orifices, order the necessary parts via Carrier RCD. See
Table 10 for available orifice sizes. See Table 11 and
Table 12 for orifice sizes for Natural Gas and LP fuel
usage at various elevations above sea level.
Check that each replacement orifice is tight at its threads
into the manifold pipe and that orifice projection does not
exceed maximum value. See Fig. 32.
48TC
Summary of Contents for WeatherMaker 48TC*A04
Page 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Page 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Page 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Page 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Page 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...
Page 65: ...65 C08317 Fig 84 48TC Unit Wiring Diagram Control A06 48TC ...