Table 27 – EconoMi$er IV Input/Output Logic
INPUTS
OUTPUTS
Demand Control
Ventilation (DCV)
Enthalpy*
Y1
Y2
Compressor
N Terminal†
Outdoor
Return
Stage
1
Stage
2
Occupied
Unoccupied
Damper
Below set
(DCV LED Off)
High
(Free Cooling LED
Off)
Low
On On
On
On
Minimum position
Closed
On Off
On
Off
Off Off
Off
Off
Low
(Free Cooling LED
On)
High
On On
On
Off
Modulating** (between
min. position and full-
open)
Modulating** (be-
tween closed and
full-open)
On Off
Off
Off
Off Off
Off
Off
Minimum position
Closed
Above set
(DCV LED On)
High
(Free Cooling LED
Off)
Low
On On
On
On
Modulating†† (between
min. position and DCV
maximum)
Modulating†† (be-
tween closed and
DCV
maximum)
On Off
On
Off
Off Off
Off
Off
Low
(Free Cooling LED
On)
High
On On
On
Off
Modulating***
Modulating†††
On Off
Off
Off
Off Off
Off
Off
*
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
†
Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
** Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
C06053
Fig. 74 -- EconoMi$er IV Functional View
EconoMi$er IV
Table 27 provides a summary of EconoMi$er IV.
Troubleshooting instructions are enclosed.
A functional view of the EconoMi$er is shown in Fig. 74.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is
available from Carrier to help with EconoMi$er IV
training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10
to 20 mA device used to measure the outdoor-air
temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling. The sensor is factory-installed on the
EconoMi$er IV in the outdoor airstream. (See Fig. 75.)
The operating range of temperature measurement is 40
_
to
100
_
F (4
_
to 38
_
C). See Fig. 77.
48TC
Summary of Contents for WeatherMaker 48TC*A04
Page 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Page 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Page 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Page 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Page 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...
Page 65: ...65 C08317 Fig 84 48TC Unit Wiring Diagram Control A06 48TC ...