If the calculated IAQ minimum position is greater than
the IAQ maximum damper position configuration then it
will be clamped to the configured value.
Demand Limit
If the RTU--MP receives a level 1 (one degree offset), 2
(two degree offset), or a 3 (4 degree offset) to the BACnet
demand limit variable, the controller will expand the
heating and cooling setpoints by the configured demand
limit setpoint value and remain in effect until the BACnet
demand limit variable receives a 0 value.
FASTENER TORQUE VALUES
See Table 32 for torque values.
Table 32 – Torque Values
Supply fan motor mounting
120 +/--- 12 in---lbs
Supply fan motor adjustment plate
120 +/--- 12 in---lbs
Motor pulley setscrew
72+/--- 5 in---lbs
Fan pulley setscrew
72+/--- 5 in---lbs
Blower wheel hub setscrew
72+/--- 5 in---lbs
Bearing locking collar setscrew
65---70 in---lbs
Compressor mounting bolts
65---75 in---lbs
Condenser fan motor mounting bolts
20 +/--- 2 in---lbs
Condenser fan hub setscrew
84 +/--- 12 in---lbs
48TC
Summary of Contents for WeatherMaker 48TC*A04
Page 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Page 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Page 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Page 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Page 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...
Page 65: ...65 C08317 Fig 84 48TC Unit Wiring Diagram Control A06 48TC ...