Table 21 – RTU--MP Controller Inputs and Outputs
POINT NAME
BACnet OBJECT
NAME
TYPE OF I/O
CONNECTION PIN
NUMBERS
INPUTS
Space Temperature Sensor
sptsens
AI (10K Thermistor)
J20---1, 2
Supply Air Temperature
sat
AI (10K Thermistor)
J2---1, 2
Local Outside Air Temperature Sensor
oatsens
AI (10K Thermistor)
J2---3, 4
Space Temperature Offset Pot
sptopot
AI (100K Potentiometer)
J20---3
Indoor Air Quality
iaq
AI (4---20 ma)
J4---2, 3
Outdoor Air Quality
oaq
AI (4---20 ma)
J4---5, 6
Safety Chain Feedback
safety
DI (24 VAC)
J1---9
Compressor Safety
compstat
DI (24 VAC)
J1---2
Fire Shutdown
firedown
DI (24 VAC)
J1---10
Enthalpy Switch
enthalpy
DI (24 VAC)
J2---6, 7
Humidistat Input Status
humstat
DI (24 VAC)
J5---7, 8
CONFIGURABLE INPUTS*
Space Relative Humidity
sprh
AI (4---20 ma)
J4---2,3 or J4---5,6
Outside Air Relative Humidity
oarh
AI (4---20 ma)
Supply Fan Status
fanstat
DI (24 VAC)
J5---1,2 or J5---3,4 or
J5 5,6 or J5---7,8
Filter Status
filtstat
DI (24 VAC)
Remote Occupancy Input
remocc
DI (24 VAC)
OUTPUTS
Economizer Commanded Position
econocmd
4---20ma
J2---5
Supply Fan Relay State
sf
DO Relay (24VAC , 1A)
J1---4
Compressor 1 Relay State
comp_1
DO Relay (24VAC , 1A)
J1---8
Compressor 2 Relay State
comp_2
DO Relay (24VAC , 1A)
J1---7
Heat Stage 1 Relay State
heat_1
DO Relay (24VAC , 1A)
J1---6
Heat Stage 2 Relay State
heat_2
DO Relay (24VAC , 1A)
J1---5
Power Exhaust Relay State
aux_2
DO Relay (24VAC , 1A)
J11---3
Dehumidification Relay State
humizer
DO Relay (24VAC, 1A)
J11---7, 8
LEGEND
AI
--- Analog Input
AO
--- Analog Output
DI
--- Discrete Input
DO
--- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.
Refer to the input configuration and accessory sections for more detail.
NOTE
:
Refer to Form 48--50H--T--2T for complete
configuration of RTU--MP, operating sequences and
troubleshooting information. Refer to
RTU--MP 3rd Party
Integration Guide
for details on configuration and
troubleshooting of connected networks. Have a copy of
these manuals available at unit start--up.
The RTU--MP controller requires the use of a Carrier
space sensor. A standard thermostat cannot be used with
the RTU--MP system.
Supply
Air
Temperature
(SAT)
Sensor
--
On
FIOP--equipped 48TC unit, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6--inches (12.7
mm) in length. It is a nominal 10--k ohm thermistor. See
Table 15 for temperature--resistance characteristic.
The SAT is factory--wired. The SAT probe is wire--tied to
the supply--air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re--position the sensor in the flange of the supply--air
opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2--in. hole in the flange or duct.
Use two field--supplied, self--drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 41.
Outdoor Air Temperature (OAT) Sensor -- The OAT is
factory--mounted in the EconoMi$er 2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an
eyelet
mounting
ring.
See
Table
15
for
temperature--resistance characteristic.
EconoMi$er 2 -- The RTU--MP control is used with
EconoMi$er2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the RTU--MP control; EconoMi$er 2 has no internal
logic device.
Outdoor air management functions can be enhanced with
field--installation of these accessory control devices:
Enthalpy control (outdoor air or differential sensors)
Space CO
2
sensor
Outdoor air CO
2
sensor
Field Connections -- Field connections for accessory
sensors and input devices are made the RTU--MP, at plugs
J1, J2, J4, J5, J11 and J20. All field control wiring that
48TC
Summary of Contents for WeatherMaker 48TC*A04
Page 10: ...10 COOLING CHARGING CHARTS cont C08204 C08228 Fig 12 cont Cooling Charging Charts 48TC ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08229 C08437 Fig 12 cont Cooling Charging Charts 48TC ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08438 C08439 Fig 12 cont Cooling Charging Charts 48TC ...
Page 35: ...35 C08248 Fig 42 PremierLink Wiring Schematic 48TC ...
Page 43: ...43 C07129 Fig 59 RTU MP Multi Protocol Control Board 48TC ...
Page 44: ...44 44 C08458 Fig 60 RTU MP System Control Wiring Diagram 48TC ...
Page 64: ...64 C08308 Fig 83 48TC Typical Unit Wiring Diagram Power A06 208 230 3 60 48TC ...
Page 65: ...65 C08317 Fig 84 48TC Unit Wiring Diagram Control A06 48TC ...