Installing the UPC Open
UPC Open
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2017
Installation and Integration Guide
All rights reserved
9
Color Code
Black, white, green, red
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC drain wire, terminated
at controller
UL temperature rating
32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
ZS Sensor overview
ZS Sensors are thermistor-based temperature sensors that may optionally sense humidity, CO
2
, or VOC. ZS
Sensors are wired to the Rnet port on i-Vu® Open controllers.
REQUIREMENTS
•
A v6.5 or later i-Vu® system
•
v6.04.xxx or later controller drivers
You can use the following ZS sensors:
•
ZS Standard
•
ZS Plus
•
ZS Pro
NOTES
•
A control program can use no more than 5 ZS Sensors, so you must use 2 control programs if your Rnet
network has 10 sensors.
•
The ZS CO2 model uses 190 mA during sample period. Use auxiliary 12 Vdc, unless it is the only device on
the Rnet port.
For basic user instructions, see the
ZS Sensor User Guide
. For detailed installation instructions, see the
ZS
Sensors Installation Guide
.
SPT sensor overview
The UPC Open is connected to a wall-mounted space temperature sensor to monitor room temperature. Wire SPT
sensors to the UPC Open's
Rnet
port.
The UPC Open supports the following:
•
SPT Standard
•
SPT Plus
•
SPT Pro
For basic user instructions, see the
SPT Sensors Owner Guide
. For more detailed instructions, see the
Carrier
Sensors Installation Guide
.
NOTE
If the Rnet has multiple SPT Standard sensors, you must give each a unique address on the Rnet.