What is the TV-UCXP683T-V?
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
5
Environmental operating
range
-4 to 158°F (-20 to 70°C), 10-95% relative humidity, non-condensing
NOTES
•
The TV-UCXP683T-V is suitable for installation inside or outside the building
envelope.
•
Install in a UL Listed enclosure only.
•
Do not change the position of the
End of Net
switch at temperatures below -
22°F (-30C) to ensure proper operation and electrical connectivity.
Physical
Fire-retardant plastic ABS, UL94-5VA
Terminal blocks and
connectors
Screw-type terminal blocks.
0.2 in (5.08 mm) pitch connectors
Mounting
35mm DIN rail mounting or screw mounting
Overall dimensions
A:
B:
Depth:
7.78 in. (19.77 cm)
5.88 in. (14.94 cm)
2.00 in. ( 5.09 cm)
Screw mounting dimensions C:
D:
5.3 in (13.45 cm)
4.50 in. (11.43 cm)
Air flow sensors
E:
F:
G:
.49 in. (1.26 cm)
1.96 in. (4.98 cm)
.41 in. (1.05 cm)
Weight
1.2 lbs (0.54 kg)
BACnet support
Conforms to the BACnet Advanced Application Controller (B-AAC) and B-BBMD
Standard Device Profiles as defined in ANSI/ASHRAE Standard 135-2012 (BACnet)
Annex L, Protocol Revision 14
Compliance
United States of America:
FCC CFR, Part 15, Class B
Canada:
Industry Canada Compliant, ICES-003, Class A
cUL Listed UL 916, PAZX7, Energy Management Equipment
Europe:
Mark
EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in
residential, commercial and light industry environment
EN50491-3:2009, Part 3: Electrical safety requirements for Home and Building
Electronic Systems (HBES) and Building Automation and Control Systems (BACS)
Low Voltage Directive: 2014/35/EU
RoHS Compliant: 2015/863/EU
Summary of Contents for TruVu UCXP683T-V
Page 75: ......