What is the TV-UCXP683T-V?
TruVu™ UCXP683T
-V
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
2
You can use the TV-UCXP683T-V's physical communication ports as follows:
Port
Port type
For this type of
communication...
At...
Eth0
Eth1
10/100 Mbps Ethernet*
BACnet/IP,
BACnet/Ethernet, and/or
Modbus TCP/IP
10 or 100 Mbps
S1
High-speed EIA-485 port
BACnet/MSTP
or
Modbus Serial
9.6 to 115.2 kbps
9.6 to 115.2 kbps
I/O Bus
Electrically isolated EIA-485 port I/O expanders (future)
* The Ethernet ports can run Modbus simultaneously with either BACnet/IP or BACnet/Ethernet.
The TV-UCXP683T-V also has the following ports:
•
Rnet port for connecting ZS sensors, an Equipment T
ouch, an TruVu™ ET Display, and Wireless Adapter for
wireless sensors
•
Service USB port for connecting locally to controller setup pages, the TruVu™ ET Display, or the Carrier
wireless service adapter
•
Comm USB port for other communication options in the future
•
Act Net port supports a combination of up to 5 Act Net addresses, as follows:
○
Address
1
is reserved for the Carrier actuator
○
Address
2
and
3
are reserved for the VAV Zone II Secondary Duct
○
Address
4
and
5
for i-Vu® Smart Valves
Specifications
Driver
drv_fwex_< version >.driverx
Maximum number of control programs*
10
Maximum number of BACnet objects*
12000
Third-party BACnet integration points
NOTE
Must be on the BACnet/IP network
1050
Third-party Modbus integration points
50
* Depends on available memory.