![background image](http://html1.mh-extra.com/html/carrier/truvu-eqt2/truvu-eqt2_installation-and-startup-manual_2563784010.webp)
Wiring the TruVu™ ET display
TruVu™ ET Display (part# EQT2)
CARRIER CORPORATION ©2020
Installation and Start-up Guide
All rights reserved
6
Wiring for Communication - Rnet configuration
You can connect the TruVu™ ET display to a controller's Rnet port using 2-conductor wire 22 AWG. The Rnet can
have one TruVu™ ET display, plus ZS sensors and/or a wireless adapter that communicates with wireless sensors.
NOTE
The TruVu™ ET display:
•
Cannot share the Rnet with an Equipment Touch.
•
Does not get its power from the Rnet; it must be powered by an external 24 Vdc DC power source.
•
Must be within 500 feet (152 meters).
CAUTION
The TruVu™ ET display can share a power supply with the controller as long as:
•
The power source shared by the controller and TruVu ET display is DC power.
•
The same polarity is maintained.
•
The power source is used only for Carrier Corporation® controllers.
CAUTION
If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
Summary of Contents for TruVu EQT2