background image

4

Installing with Indoor Piston

Outdoor Unit Connected to Factory Approved Indoor Unit

Check piston size shipped with indoor unit to see if it matches

required indoor piston size. If it does not match, replace indoor
piston with correct piston size.

NOTE

: Correct pistons are shipped with outdoor units in the

accessory bag and are only qualified for piston fan coils. Example
fan coils with piston: FB4C and FY5B (1.5 through 4 ton)
When changing indoor piston, use a back

up wrench. Hand

tighten hex nut, then tighten with wrench 1/2 turn. Do not exceed

30 ft

lbs. The indoor piston contains a Teflon ring (or seal) which

is used to seat against the inside of distributor body, and must be
installed properly to ensure proper seating. See Fig. 5

13/16” BRASS HEX NUT

TEFLON

®

 SEAL

TEFLON

®

RINGS

3/4” BRASS HEX BODY

“H” DISTRIBUTOR

PISTON RETAINER

PISTON

A10342

Fig. 5 -- Indoor (Cooling) Piston

CAUTION

!

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If using a TXV in conjunction with a single--phase

reciprocating compressor, a compressor start capacitor and

relay are required.

Units with Cooling Mode TXV

Units installed with cooling mode TXV require charging by the

subcooling method.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure liquid service valve pressure by attaching an accur-

ate gage to service port.

3. Measure liquid line temperature by attaching an accurate

thermistor type or electronic thermometer to liquid line near

outdoor coil.

4. Refer to unit rating plate for required subcooling temperat-

ure.

5. Refer to Table 2 --

Rating Plate (required) Subcooling Tem-

perature

. Find the point where required subcooling temper-

ature intersects measured liquid service valve pressure.

6. To obtain required subcooling temperature at a specific li-

quid line pressure, add refrigerant if liquid line temperature
is higher than indicated or reclaim refrigerant if temperature
is lower. Allow a tolerance of

3

_

F (

1.7

_

C).

Units with Indoor Piston

Units installed with indoor pistons require charging by the

superheat method.
The following procedure is valid when indoor airflow is within

21 percent of its rated CFM.

1. Operate unit a minimum of 15 minutes before checking

charge.

2. Measure suction pressure by attaching an accurate gage to

suction valve service port.

3. Measure suction temperature by attaching an accurate ther-

mistor type or electronic thermometer to suction line at ser-
vice valve.

4. Measure outdoor air dry bulb temperature with thermo-

meter.

5. Measure indoor air (entering indoor coil) wet--bulb temper-

ature with a sling psychrometer.

6. Refer to Table 3 --

Superheat Charging -- AC Only

. Find

outdoor temperature and evaporator entering air wet--bulb
temperature. At this intersection, note superheat. Where a
dash (----) appears on the table, do not attempt to charge sys-

tem under these conditions or refrigerant slugging may oc-
cur. Charge must be weighted in, adding or removing 0.6

oz/ft of 3/8 liquid line above or below 15 feet (4.6m) re-
spectively.

7. Refer to Table 4 --

Required Suction--Line Temperature

.

Find superheat temperature (from #6 above) and suction
pressure. At this intersection, note suction line temperature.

8. If unit has a higher suction line temperature than charted

temperature, add refrigerant until charted temperature is

reached.

9. If unit has a lower suction line temperature than charted

temperature, reclaim refrigerant until charted temperature is

reached.

10. When adding refrigerant, charge in liquid form into suction

service port using a flow--restricting device.

11. If outdoor air temperature or pressure at suction valve

changes, charge to new suction line temperature indicated

on chart.

12. Optimum performance will be achieved when the operating

charge produces 10

_

F suction superheat at suction service

valve with 95

_

F (35

_

C) outdoor ambient and 80

_

F (27

_

C)

dry bulb (67

_

F / 19

_

C) wet bulb) indoor temperature (DOE

“A” test conditions) at rated airflow.

24AC

B

/24AC

C

Summary of Contents for Single-Stage Comfort 24ACB

Page 1: ...must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION INSTRUCTIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tub...

Page 2: ...ieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves Federal regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper ...

Page 3: ...of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant...

Page 4: ...perature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The following procedure is valid when indoor airflow is within 21 percent of its rated CFM 1 Operate unit a minimum of 15 minutes before checking charge 2 Measure suction pressure by att...

Page 5: ...6 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 Table 3 Superheat Charging AC Only OUTDOOR TEMP _F EVAPORATOR ENTERING AIR TEMPERATURE _F WB 50 52 54 56 58 60 62 64 67 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 ...

Page 6: ... 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 ...

Page 7: ...rical wire or metal conduit when installed in accordance with existing electrical codes Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 6 DISCONNECT PER N E C AND OR LOCAL CODES CONTACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24 ...

Page 8: ...eset Adjust charge by adding or removing 0 6 oz ft of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to sta...

Page 9: ...700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a s...

Page 10: ...rris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ACB C 3SI Replaces 24ACB C 2SI 24ACB 24ACC ...

Reviews: