background image

2

INSTALLATION

Check Equipment and Job Site

UNPACK UNIT
Move to final location. Remove carton taking care not to damage

unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner

panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie

down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2

to determine base pan size and knockout hole location.
For hurricane tie downs, contact local distributor for details and PE

(Professional Engineer) certification, if required by local

authorities.
On rooftop applications, mount on level platform or frame. Place

unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.

Consult the Application Guideline and Service Manual --
Residential Split System Air Conditioners and Heat Pumps for

wind baffle construction.

NOTE

:

Unit must be level to within

±

2

_

(

±

3/8 in./ft.) per

compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 24 in. (609.6 mm)
clearance to service end of unit and 48 in. (1219.2 mm) (above

unit. For proper airflow, a 6--in. (152.4 mm) clearance on 1 side of
unit and 12--in. (304.8 mm) on all remaining sides must be

maintained. Maintain a distance of 24 in. (609.6 mm) between

units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit at least 6 in. (152.4 mm) above
roof surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode without

accessory is 55

_

F (12.78

_

C), and the maximum outdoor

operating ambient in cooling mode is 125

_

F (51.67

_

C).

Make Piping Connections

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could result in personal injury

or death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal. Use all service ports and open

all flow--control devices, including solenoid valves.
Federal regulations require that you do not vent refrigerant

to the atmosphere. Recover during system repair or final

unit disposal.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
If ANY refrigerant tubing is buried, provide a 6--in. vertical

rise at service valve. Refrigerant tubing lengths up to 36--in.

may be buried without further special consideration. Do not

bury lines more than 36--in. (914.4 mm).

3/8---in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

UNIT BASE PAN

Dimension

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

26 X 26

9–1/8 (231.8)

4–7/16 (112.7)

21–1/4 (539.8)

31–1/2 X 31–1/2

9–1/8 (231.8)

6–9/16 (166.7) 24–11/16 (627.1)

35 X 35

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

A05177

Fig. 2 -- Tiedown Knockout Locations

Outdoor units may be connected to indoor section using accessory
tubing package or field--supplied refrigerant grade tubing of correct

size and condition. Rated tubing diameters shown in Table 1 are
recommended up to 80 ft. (24.38 m). See Product Data for

acceptable alternate vapor diameters and associated capacity losses.
For tubing requirements beyond 80 ft. (24.38 m), substantial

capacity and performance losses can occur. Following the

recommendations in the Longline Guideline will reduce these
losses. Refer to Table 1 for field tubing diameters. Refer to Table 5

for accessory requirements.
There are no buried--line applications greater than 36--in. (914.4

mm) allowed.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and

moisture in the system.

Outdoor Unit Connected to Factory Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for
operation with factory approved AHRI rated indoor unit when

connected by 15 ft. (4.57 m) of field--supplied or factory--accessory
tubing, and factory supplied filter drier. Check refrigerant charge

for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid
service valves (see Table 1.) Use refrigerant grade tubing

Sweat Connection

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat--sinking material

such as a wet cloth while brazing.

24AC

B

/24AC

C

Summary of Contents for Single-Stage Comfort 24ACB

Page 1: ...must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION INSTRUCTIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tub...

Page 2: ...ieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves Federal regulations require that you do not vent refrigerant to the atmosphere Recover during system repair or final unit disposal CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper ...

Page 3: ...of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liquid tube to the indoor coil 2 Wrap filter drier with damp cloth 3 Braze filter drier to above 5 in 127 mm liquid tube Flow arrow must point towards indoor coil 4 Connect and braze liquid refrigerant...

Page 4: ...perature is higher than indicated or reclaim refrigerant if temperature is lower Allow a tolerance of 3_F 1 7_C Units with Indoor Piston Units installed with indoor pistons require charging by the superheat method The following procedure is valid when indoor airflow is within 21 percent of its rated CFM 1 Operate unit a minimum of 15 minutes before checking charge 2 Measure suction pressure by att...

Page 5: ...6 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47 114 46 112 44 110 43 462 122 50 120 49 118 48 116 47 114 46 112 44 474 124 51 122 50 120 49 118 48 116 47 114 46 Table 3 Superheat Charging AC Only OUTDOOR TEMP _F EVAPORATOR ENTERING AIR TEMPERATURE _F WB 50 52 54 56 58 60 62 64 67 68 70 72 74 76 55 9 12 14 17 20 23 26 29 32 35 37 40 42 ...

Page 6: ... 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85 36 71 ...

Page 7: ...rical wire or metal conduit when installed in accordance with existing electrical codes Connect Ground and Power Wires Connect ground wire to ground connection in control box for safety Connect power wiring to contactor as shown in Fig 6 DISCONNECT PER N E C AND OR LOCAL CODES CONTACTOR GROUND LUG FIELD GROUND WIRING FIELD POWER WIRING A91056 Fig 6 Line Connections Connect Control Wiring Route 24 ...

Page 8: ...eset Adjust charge by adding or removing 0 6 oz ft of 3 8 liquid line above or below 15ft 4 57 m respectively For standard refrigerant line lengths 80 ft 24 38 m or less allow system to operate in cooling mode at least 15 minutes If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to sta...

Page 9: ...700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers in line longer than 72 hours S Do not install a s...

Page 10: ...rris St S Indianapolis IN 46231 Printed in U S A Edition Date 07 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ACB C 3SI Replaces 24ACB C 2SI 24ACB 24ACC ...

Reviews: