– 26 –
5-3. High Wall Type
RAV-SP180KRT-UL, RAV-SP240KRT-UL
No.
1
2
3
4
5
Parts Name
Fan motor (for indoor)
Grille motor
Thermo. Sensor (TA sensor)
Heat exchanger sensor (TC sensor)
Heat exchanger sensor (TCJ sensor)
Type
ICF-340U30-1
MP24Z3T
318mm
Ø6,800mm
Ø6,800mm
Specications
Output (Rated) 30W, 340V DC
Output (Rated) 1W, 16 poles DC
10k
Ω
at 77°F (25°C)
10k
Ω
at 77°F (25°C)
10k
Ω
at 77°F (25°C)
n
Name of Each Part
Earth screw
Earth screws are provided
in the electric parts box.
Air outlet / Louver
Change the direction of the air to be
discharged according to cool/heat mode.
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dirt or dust.
(Provided in the air inlet grille)