– 157 –
Fixing band
Fixing band
Drain pump stand
Drain pump stand
Fixing screw
Fixing screw “B”
Fixing screw “B”
Fixing band
“A” (Ø4 ×10)
xing screws
Fixing screws
g
“A” (Ø4 ×10)
Drain pump stand
Fixing band
Heat exchanger
Fixing screws
Fixing screws “B”
(Ø4
4 ×10)
10)
Fixing screws “B”
(Ø4 ×10)
Piping cover
Fixing screws
No.
11
Part name
Heat
exchanger
Procedure
1. Detachment
1) Recover the refrigerant gas.
2) Carry out work of Detachment of
10
.
3) Remove refrigerant pipe at indoor unit side.
4) Remove the fixing screws and then
remove the piping cover.
(M4, 10 mm, 3 pcs.)
5) Remove the drain hose from the drain
pump and remove the fixing screws “A” to
remove the drain pump stand.
(M4, 8 mm, 3 pcs.)
6) While pushing the heat exchanger, remove
the fixing band, fixing screws “B” and the
heat exchanger. (M4, 8 mm, 3 pcs.)
2. Attachment
1) Mount the heat exchanger with the fixing
band and the fixing screws “B”.
(M4, 8 mm, 3 pcs.)
2) Fix the parts as before in order of drain
pump stand
→
piping cover.
3) Connect the refrigerant pipe as before and
then apply vacuuming.
4) Following to work of Attachment of
10
,
attach the parts as before.
Remarks